- 11 -
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Refrigeration Cycle Diagram
Heat Pump
• If 60K Model is installed at a distance of 15m, 525g of refrigerant should be added
(15-7.5) x 70g = 525g
30k Btu/h
5/8" 3/8" 7.5 30 5 15 70
36k Btu/h
5/8" 3/8" 7.5 30 5 15 50
42k
Btu
/h 3/4'' 3/8" 7.5 30 5 15 70
48k
Btu
/h 3/4'' 3/8" 7.5 30 5 15 70
60k
Btu
/h 3/4'' 3/8" 7.5 30 5 15 70
72k
Btu
/h 1'' 1/2" 7.5 25 5 20 70
90k
Btu
/h 9/8'' 5/8" 7.5 30 5 20 90
100k
Btu
/h 9/8'' 5/8" 7.5 30 5 20 100
Capacity
Gas Liquid
Elevation B(m)
Piping Length
A(m)
* Additional
Refrigerant
(g/m)
Pipe Size (Diam-
eter: Ø)
inch
Standard
Standard
Max.
Max.
Capacity Orifice Number
30k 63
36k 62
42k 74/72
48k 86/90
72k 98
90k 84
100k 104
Orifice Number