18 | PRODUCT DATA
Single Zone Wall Mounted Extended Piping Engineering Manual
Due to our policy of continuous product innovation, some specications may change without notication.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG ” is a registered trademark of LG Corp.
INDOOR UNIT ACOUSTIC DATA
Figure 4: Indoor Unit Sound Levels
Model H M L
LSN243HLV 49 44 40
LSN303HLV 49 44 40
LSN363HLV 49 44 40
Table 7: Indoor Unit Sound Pressure Data
• Measurements are taken 3.28 ft away from the front of the unit.
• Sound pressure levels are measured in dB(A) with a tolerance of
±3.
• Sound pressure levels are tested in an anechoic chamber under
ISO Standard 3745.
• Sound level will vary depending on a range of factors including the
construction (acoustic absorption coefficient) of a particular room in
which the unit was installed.
Figure 5: LSU243HLV, LSU303HLV, LSU363HLV
Octave Band Center Frequency (Hz)
Octave Band Sound Pressure Level (0dB = 20μPa)
10
20
30
40
50
60
70
80
63 125 250 500 1000 2000 4000 8000
NC-15
NC-20
NC-25
NC-30
NC-35
NC-40
NC-45
NC-50
NC-55
NC-60
NC-65
Approximate
Hearing
Threshold