CONDENSATE PIPING
Vertical/Horizontal AHU Condensation Drain Pipe Installation
•  Drain piping must slope down or ow may reverse back to unit.
•  During drain piping connection, be careful not to exert extra force on 
the drain port on the indoor unit.
•  Refer to Table 23 for drain pipe sizing.
•  Use polyvinyl chloride pipe.
1.  Refer to Figure 48 and plan the drain pipe routing so that the pipe 
will slope downward from the indoor unit to its end drain location.
2.  Connect the provided flexible drain pipe to the main drain pipe.
3.  Pour water into the flexible pipe as shown in Figure 50 to test for 
leaks. Repair leaks if necessary.
4.  Route the flexible drain pipe to the indoor unit and connect the 
flexible drain pipe to the drain port of the indoor unit.
5.  Install field supplied polyethylene foam insulation 5/16 inch thick 
or greater on the flexible drain pipe and position snugly against 
indoor unit.
Figure 46: Vertical / Horizontal Air Handler Unit Drain Piping System.
Figure 47: Vertical / Horizontal Air Handler Unit U-Trap Specications.
U-Trap
B
C
A  ≥
 2-3/4 inch 
B  ≥ 2C
C  ≥ 2 x SP
SP = External Pressure
(in. WG)
Ex) External Pressure
= 0.39 in. WG
A  ≥ 2-3/4 inches
B  ≥ 1-9/16 inches
C  ≥ 25/32 inches
A
Applied U-Trap Dimensions
• Install the U-Trap to prevent leaks 
  caused by blocking the intake air filter.
3/4 inch
connector
Vertical/Horizontal Air Handler Unit (AHU) Drain Information
Note:
Install a eld-supplied external condensate pan underneath the entire 
vertical air handling unit to avoid damage due to condensate overow. 
Vertical / Horizontal Air Handler units have a gravity drain.
•  Avoid blocking lter access panel when connecting drain lines.
•  An additional external condensate line should run from the unit into 
the pan.
•  The entire condensate line should be drained from the external 
condensate pan. 
•  Point the drain hose downward for easy drain ow.
• 
 Do not use pipe joint connection or PVC/CPVC for the unit drain 
line connection. Use Teon® tape.
Maintenance
drain port
Upward
routing
not allowed
Pipe clamp
Indoor unit
Figure 48: Drain Piping Slope.
Flexible drain hose
Figure 49: Do Not Sharply Bend Drain Pipe.
Pour water to
test for proper
drainage and
no leaks 
Drain Pump
Drain pan
Flexible drain hose
Main drain pipe
Glue the joint
Drain
port
Drain hose clip (provided)
Figure 50: Testing the Drain Pipe.
Upflow Drain Horizontal-left Drain
Horizontal-left 
Drain Knockout
Air filter cover
Main drain along with suitable trap.
( Field supplied trap with sufficient 
depth can be used. P-traps of standard 
size are not sufficient. Refer the figure 
for recommended condensate trap.)
Supplementary drain 
with proper trap. (field 
supplied kit can be used)