2. Specifications
Ceiling Concealed Duct(High Static) _ 3
Indoor Units
Notes:
1. Capacities are based on the following conditions:
    Cooling    • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB
                    • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB
                    • Interconnecting Piping Length 7.5m
                    • Level Difference of Zero
    Heating   • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB
                    • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB
                    • Interconnecting Piping Length 7.5m
                    • Level Difference of Zero
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without prior notification
4. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter
should be considered for electrical work and design. Especially the power cable and circuit breaker should be select-
ed in accordance with that.
5. EEV : Electronic Expansion Valve
6. Sound pressure levels are measured at 50Pa External Static Pressure condition.
7. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. 
The values depends on the ambient conditions and values are normally higher in actual operation.
Conversion Formula
kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m
3
/min x 35.3
l/s = CMM x 1000/60 
 Type
 Model                               Unit
                                                                       kW
 Cooling Capacity                                         kcal/h
                                                                      Btu/h
                                                                       kW
 Heating Capacity                                         kcal/h
                                                                      Btu/h
 Casing  
 
Dimensions(WxHxD)
 
Body
                                 mm
                                                                       inch
 
Coil
 
Rows x Columns x FPI
 
                             Face Area                          m
2
                             Type  
 
Motor Output x Number           
W
                             Running Current                 A
 
Air Flow Rate(H / M / L)
       CMM
 
(High Mode-factory set)
        cfm
 Fan  
External Static Pressure
 mmAq(Pa)
 
Air Flow Rate(H / M / L)
       CMM
                             (Standard Mode)               cfm
 
External Static Pressure
 mmAq(Pa)
                             Drive  
                             Motor type  
 Temperature Control  
 Sound Absorbing Thermal Insulation Material
 Air Filter
 Safety Device  
 
 
Liquid Side                    mm(inch)
 
Pipe Connections
  Gas Side                       mm(inch)
 
Drain Pipe(Internal Dia.)
     mm(inch)
 Net Weight                                                  kg(lbs)
 
Noise Level
(Sound Pressure, 1.5m, H / M / L)
       dB(A)
 Power Supply                                            Ø, V, Hz
 Refrigerant Control 
 Transmission cable                                      mm
2
ARNU36GBGA4
10.6
9,100
36,200
11.9
10,200
40,600
Galvanized Steel Plate
1,182 x 298 x 450 
46-17/32 x 11-23/32 x 17-23/32 
3 x 12 x 21
0.26
Sirocco Fan
350
2.65
32.3 / 29.0 / 25.3
1,141 / 1,024 / 894
10(98)
28.4 / 25.3 / 21.8
1,003 / 894 / 770
8(78)
Direct
BLDC
Microprocessor, Thermostat for cooling and heating
Foamed polystrene
-
Fuse
Ø9.52(3/8)
Ø15.88(5/8)
25(1)
38(83.8)
33 / 31 / 28    
1, 220-240, 50
1, 220, 60
EEV
CVV-SB 1.0~1.5 x 2C
 ARNU42GBGA4               ARNU48GBRA4
                 12.3                                   14.1
               10,600                               12,100
               42,000                               48,100
                 13.8                                   15.9
               11,800                               13,600
               47,000                               54,200
  Galvanized Steel Plate      Galvanized Steel Plate
      1,182 x 298 x 450              1,230 x 380 x 590 
 46-17/32 x 11-23/32 x 17-23/32       48-7/16 x 14-31/32 x 23-7/32
           3 x 12 x 21                         3 x 13 x 19
                 0.26                                   0.38 
           Sirocco Fan                       Sirocco Fan
                 350                                 185 x 2
                 2.65                                    3.5 
       34.5 / 32.3 / 30.7               44.8 / 40.6 / 33.3
    1,218 / 1,141 / 1,084         1,582 / 1,434 / 1,176
               10(98)                               14(137)
       32.0 / 28.4 / 27.2               44.4 / 39.5 / 33.5
     1,130 / 1,003 / 961           1,568 / 1,395 / 1,183
                8(78)                                 10(98)
               Direct                                 Direct
               BLDC                                 BLDC
  Microprocessor, Thermostat for cooling and heating       Microprocessor, Thermostat for cooling and heating
     Foamed polystrene           Foamed polystrene
                    -                                         -
                Fuse                                  Fuse
            Ø9.52(3/8)                         Ø9.52(3/8)
           Ø15.88(5/8)                       Ø15.88(5/8)
                25(1)                                  25(1)
             38(83.8)                             53(117)
           36 / 33 / 30                        38 / 36 / 34 
         1, 220-240, 50                   1, 220-240, 50
            1, 220, 60                          1, 220, 60
                 EEV                                   EEV
   CVV-SB 1.0~1.5 x 2C       CVV-SB 1.0~1.5 x 2C
Ceiling Concealed Duct(High Static)