During the installation of the unit, consider service, inlet, and outlet and acquire the minimum
space as shown in the figures below.
14
INSTALLATION SPACE
ENGLISH
Category
Installation Space
Case 1
(10mm≤Side Space≤49mm)
Case 2
(Side Space≥49mm)
4 sides
are
walls
•
The height of the wall on the front side must be 1500mm(59-1/16”) or less.
•
The height of the wall on the inlet side must be 500mm(19-11/16”) or less.
• There is no limit to the wall on the side.
• If the height of the walls on the front and the side are higher than
the limit, there must be additional space on the front and the side.
- Additional Space on the front side by 1/2 of h1.
- Additional Space on the inlet side by 1/2 of h2
- h1 = A(Actual height) - 1500mm(59-1/16”)
- h2 = B(Actual height) - 500mm(19-11/16”)
Individual Installation
INSTALLATION SPACE