Function
4.8 Vacuum Mode
This function is used for creating vacuum in the system after compressor replacement, ODU parts replacement or
IDU addition/replacement.
Mode setting method
CAUTION
• ODU operation stops during vacuum mode. Compressor can't operate.
Master unit PCB DIP switch on : No.5
Select the mode using ‘▶’, ‘◀’ Button : “SVC”
Push the ‘●’ button
Select the Function using ‘▶’, ‘◀’ Button :
“Se1” Push the ‘●’ button
Start the vacuum mode : “VACC”
ODU V/V open
ODU EEV open
IDU EEV open
Using a sump heater
Push the reset button on Master unit PCB
Vacuum mode cancellation method