■ Setting the function
Select the mode/function/option/value using ‘
▶
’, ‘
◀
’ Button and confirm that using the ‘ ’ button after dip switch
No.5 is turned on.
* Functions save in EEPROM will be kept continuously, though the system power was reset.
Function
MODE FUNCTION OPTION VALUE ACTION
Remark
Content Display1 Content Display2 Content Display3 Content Display4 Implement Display5
Installation Func
Cool&Heat Selector Fn1 OFF OP1~OP2 - - -
Change the
set value
blank
save in
EEPROM
Geo thermal mode Fn2 OFF ON - - -
Change the
set value
blank
save in
EEPROM
220V Out for
Solenoid valve
Fn3 OFF ON - - -
Change the
set value
blank
save in
EEPROM
Variable water flow
control
Fn4 OFF ON - - -
Change the
set value
blank
save in
EEPROM
Outside Unit adress Fn5 - - 0~254 set the value
Change the
set value
blank
save in
EEPROM
Target pressure
adjusting
Fn7 OFF OP1~OP3 - - -
Change the
set value
blank
save in
EEPROM
Using Sump heater Fn8 OFF ON - - -
Change the
set value
blank
save in
EEPROM
SVC Svc
Vacum mode SE1 - - - -
Start opera-
tion
vAcc -
Forced oil return SE2 - - - -
Start opera-
tion
OI -
Refrigerant noise
reduction
mode
SE4 OFF ON - - -
Change the
set value
on off
save in
EEPROM
Cycle data view SE5 OP1~OP7 - - -
Show in
segment
Show the
each
numerical
value in
process
-