Part 2 Functions & Controls
Installer Setting -Test Run Mode
After installing the product, you must run a Test Run mode.
For details related to this operation, refer to the product manual.
Function Code Set
1
2
Keep pressing button setting for 4
secs to enter installer setting mode until
code displayed in timer segment.
1
Press button to start.
2
18˚C cooling, High Fan Speed, Airflow direction mode will be operated during 18 minutes with ignoring room tem-
perature.
After running 18 minutes under test run mode, system will automatically turn OFF.
In case of duct type, the Airflow UP/DOWN function is not displayed.
During test run mode, receiving signal from wireless remote controller will release this operation.
If you press any kind of button, Test Run mode will be released.