2-4. Cooling
TROUBLE DIAGNOSIS
-84-
Problems Causes Checks Measures Remarks
High  Refrigerant leak. Check sequence
Weld the leaking part, recharge the Drier must be replaced.
temperature 1. Check the welded parts of the  refrigerant.
in the freezer drier inlet and outlet and drier
compartment. auxiliary in the compressor 
compartment (high pressure side).
2. Check the end of compressor 
sealing pipe (low pressure side).
3. Check silver soldered parts.
(Cu + Fe / Fe + Fe).
4. Check bending area of wire 
condenser pipe in compressor
compartment (cracks can 
happen during bending).
5. Check other parts (compressor
compartment and evaporators in
freezer compartment).
Shortage of refrigerant. Check frost formation on the surface - Find out the leaking area, repair, Drier must be replaced.
of evaporator in the freezer  evacuate, and recharge the 
compartment. refrigerant.
- If the frost forms evenly on the  - No leaking, remove the remaining
surface, it is OK. refrigerant, and recharge new 
- If it does not, it is not good. refrigerant.