89
Single CAC Outdoor Unit
Standard Inverter
7. Capacity Coefficient Factor
7.1 Rate of change in capacity due to the main piping length
1 Phase Inverter
Rate of change in cooling capacity
Rate of change in heating capacity
3 Phase Inverter
Rate of change in cooling capacity
Rate of change in heating capacity
7.2 Calculation of actual system capacity
1. Outdoor unit standard maximum capacity
Q
max.
[from specification table]
2. Outdoor unit capacity at Ti, To temperature.
Q
(Ti, To)
[from capacity table]
3. Outdoor unit capacity coefficient factor
F
(Ti, To)
= Q
(Ti, To)
/ Q
(max.)
4. Piping correction factor
F
piping
for piping length [from capacity coefficient factor table]
5. Indoor Unit actual capacity
Q
actual
= Q
max
x F
(Ti, To)
x F
piping
Piping length(m) 5 10 15 20 30 40 50 60 70 75
Rate of change in
capacity(%)
2.5/3.5 kW 100 99.8 99.3 98.8 - -----
5.0 kW 100 99.8 99.3 98.8 97.8 -----
7.1/8.0/10.0 kW 100 99.3 97.9 96.6 93.8 91.1 88.4 - - -
12.5/14.0/15.0 kW 100 99.3 97.9 96.6 93.8 91.1 88.4 85.6 82.9 81.5
Piping length(m) 5 10 15 20 30 40 50 60 70 75
Rate of change in
capacity(%)
2.5/3.5 kW 100 99.8 99.4 99.0 - -----
5.0 kW 100 99.8 99.4 99.0 98.3 -----
7.1/8.0/10.0 kW 100 99.7 99.2 98.7 97.7 96.6 95.6 - - -
12.5/14.0/15.0 kW 100 99.7 99.2 98.7 97.7 96.6 95.6 94.6 93.5 93
Piping length(m) 5 10 15 20 30 40 50 60 70 75
Rate of change in
capacity(%)
10.0 kW 100 99.3 97.9 96.6 93.8 91.1 88.4 - - -
12.5/14.0/15.0 kW
19.0/23.0 kW
100 99.3 97.9 96.6 93.8 91.1 88.4 85.6 82.9 81.5
Piping length(m) 5 10 15 20 30 40 50 60 70 75
Rate of change in
capacity(%)
10.0 kW 100 99.7 99.2 98.7 97.7 96.6 95.6 - - -
12.5/14.0/15.0 kW
19.0/23.0 kW
100 99.7 99.2 98.7 97.7 96.6 95.6 94.6 93.5 93.0