EasyManua.ls Logo

LG UU70W - Synchro Operation Guidelines; Refrigerant Additional Charging Method

LG UU70W
37 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8
INSTALLATION OF OUTDOOR UNIT
ENGLISH
• Synchro Operation
Install the branch pipe so that pipe length and difference between high and low will not exceed
below Spec.
• Refrigerant Additional Charging Method
For additional charging method, see below table.
- When installing the branch pipe, direction and angle of installation is not limited.
- Take care so that burrs and foreign material may not enter into the cutting surface when con-
necting.
- Connect remaining those by cutting or direct insertion to the diameter of pipe.
[Unit : m]
Branch
L1
H1
A
A
L2
L3
L4
L5
H2
Remote
Controller
Pipe Length & Height Spec(MAX.)
Total(L1+L2+L3+L4+L5)
Main Pipe(L1)
Branch Pipe (L2+L3+L4+L5)
Each
Indoor-Outdoor (H1)
Indoor-Indoor (H2)
(L1+L2),(L1+L3),(L1+L4),(L1+L5)
A
80
40
40
10
30
1
70
10
Indoor Unit Refrigerant Additional charging (g)
Duo Refrigerant = (L1-b) x B + (L2 + L3) x C
Trio Refrigerant = (L1-b) x B + (L2 + L3 + L4) x C
Quartet Refrigerant = (L1-b) x B + (L2 + L3 + L4 + L5) x C
Model b (mm) B(g/m)
UU70W 25 70
Pipe Diameter.
(mm)
C (g/m)
Ø 6.35 35
Ø 9.52 40
NOTE
!
b : Rated performance for refrigerant line length.
C : Additional charging Refrigerant of Branch Liquid Pipe.
B : Additional charging Refrigerant of Main Liquid Pipe.
CAUTION
• Capacity is based on standard length and maximum allowance length is on the basis of re-
liability.
• Improper refrigerant charge may result in abnormal cycle.
!
1.MFL68645302(영) 16. 12. 7. 영영 6:09 Page 8

Related product manuals