INSTALLATION OF OUTDOOR UNIT
7
ENGLISH
- If an awning is built over the unit to prevent
direct sunlight or rain exposure, make sure
that heat radiation from the condenser is not
restricted.
- Ensure that the spaces indicated by arrows
around front, back and side of the unit.
- Do not place animals and plants in the path
of the warm air.
- Take the air conditioner weight into account
and select a place where noise and vibration
are minimum.
- Select a place so that the warm air and noise
from the air conditioner do not disturb neigh-
bors.
You need to select adequate installation location considering the following conditions, and make
sure to acquire the consent of the user.
- Place that can sufficiently endure the weight and vibration of the outdoor unit and where even
installation is possible.
- Place that has no direct influence of snow or rain
- Place with no danger of snowfall or icicle drop
- Place without weak floor or base such as decrepit part of the building or with a lot of snow ac-
cumulation
- Install at a place with fluent water draining to prevent damage from localized heavy rain and
avoid frequent flooded area.
• Single Operation
If installed tube is shorter than 25 m, addi-
tional charging is not necessary.
Additional Refrigerant
= (A-25) x Additional refrigerant (g)
INSTALLATION OF OUTDOOR UNIT
More than
300mm
Fence or
obstacles
More than 700mm
More than 600m
More than
300mm
More than
300mm
Sunroof
Unit : mm
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
Model
Pipe Size mm(inch) Length A(m) Elevation B(m)
Additional
refrigerant
(g/m)
Gas Liquid Standard Max. Standard Max.
UU70W Ø25.4(1) 9.52(3/8) 25 75 5 30 70
Installation Places
Piping length and the elevation
1.MFL68645302(영) 16. 12. 7. 영영 6:09 Page 7