Part 2   Functions & Controls
Table 1
Ceiling Concealed Duct – Low static
Model Step CMM
Static Pressure [mmAq (Pa)]
0(0) 1(10) 2(20) 3(29) 4(39) 5(49)
Setting Value
32:01 32:02 32:03 32:04 32:05 32:06
CL09R.N20
CL12R.N20
LOW 7 78 82 87 93 100 107
MID 8.5 87 91 94 100 108 116
HIGH 10 96 100 103 109 117 125
Model Step CMM
Static Pressure [mmAq (Pa)]
0(0) 1(10) 2(20) 3(29) 4(39) 5(49)
Setting Value
32:01 32:02 32:03 32:04 32:05 32:06
CL18R.N20
LOW 10 96 100 103 109 117 125
MID 12.5 109 113 117 123 130 137
HIGH 15 120 124 129 134 141 147
Model Step CMM
Static Pressure [mmAq (Pa)]
0(0) 1(10) 2(20) 3(29) 4(39) 5(49)
Setting Value
32:01 32:02 32:03 32:04 32:05 32:06
CL24R.N30
LOW 12 89 95 102 106 120 130
MID 16 102 108 115 125 131 139
HIGH 20 125 131 136 141 144 147
- The above table shows the correlation between the air rates and E.S.P.
- Be sure to set the value refering table 1. Unexpected set value will cause mal-function.
- Table 1 is based at 230 V. According to the fluctuation of voltage, air flow rate varies.