Controls
6--2
Liebert HPC--- S 006--- 022--- PD--- 273571--- 01.03.2012
iCOM Technical Data
Technical Data iCOM Medium
E2prom 4 Mbit + 512 kbit
Flash memory 32 Mbit
RAM memory 128 Mbit
Microcontroller Coldfire 32 Mbit
Analogue Input 3 x 0---10V, 0--- 5V, 4..20mA (selectable) + 2 PTC/NTC + 3 NTC
Digital Input 9 x o p t o --- c o u p l e d
Analogue Output 2 x 0 --- 1 0 V
Digital Output 7 triacs output and 2 relay output
Time and date Buffered by an LI--- battery
Hirobus Lan connectors 2 RJ45 sockets (for unit in LAN, remote display)
Ethernet network connectors 1RJ45socket
CAN bus connectors 1RJ12sockets
Hironet connectors 1 RJ10 socket for RS485 (direct connection to proprietary supervision)
RS232 service port ---
CDL Graphic Display
(special option fitted on Electrical Panel chiller board or optional for indoor
remote IP40 Box installation)
The CDL graphic display featuring a 24h / 8 days graphic record of co n-
trolled parameters as well as the last 200 events occurred.
A back ---up battery keeps the data stored in the memory (graphic data re-
cord, alarms).
D Medium graphic display (320 x 240 pixel).
D System Window: system operation status at a glance.
D Self ---explanatory Icons: they are used for the Menu---Layout of the
CDL iCOM.
D Online Help: every single parameter has its own multi ---page explana-
tion.
D Status Report of the latest 200 event/messages of the unit/system.
D Four different Graphic Data Records.
D Timer and Date mode (el e ctronic timer included in the software).
D Semi or full manual mode software management incl uding all safety devices.
D 4---Level passwords system to protect all the settings.
D Ergonomic design for use also as portable device (start---up and ”flying connections” by service per-
sonnel).
D M u l t i --- l a n g u a g e m e n u w i t h o n --- t h e --- f l y l a n g u a g e s e l e c t i o n .
CDL Technical Data
D Microcontroller: Coldfire 32 bit;.................
D Ethernet network connectors: 2 RJ45 sockets (for unit in LAN, remote display);.....
D CAN bus co nnectors: 2 RJ12 sockets;............
D Power supply: via CAN bus or external 12 Vdc supply...................
L i e b e r t H P C --- S 0 0 6 --- 0 2 2 C o n n e c t i v i t y
iCOM and CDL allow Connec t ivity with superior levels of control and supervision systems:
Hirovisor IP software
This software allows distance monitoring and telemaintenance, and also the storing in the personal com-
puter of the graphics of water temperature trends and status reports for archiving purposes. Delivery of
SMS and e---mail is supported.
BMSs connections
The IS cards and other gateway represent the communication managers portfolio which allow the integ-
ration of the L i e b e r t H P C --- S 0 0 6 --- 0 2 2 units into the most diffused Building Management Systems. The
most diffused are: SNMP, HTTP, MODBUS and LONWORK.