Set system parameters
KeepPdepressed for 3 seconds to enter into parameter setting status:
blinks, dispay shows “U10”, the 1
st
system parameter code.
Pressorto select parameter code.
PressSto show the value of the parameter.
Pressorto the value of the parameter.
PressSto return back to parameter code selection.
In this way, we can check and/or set all parameters.
KeepPdepressed for 3 seconds to save and exit the status.
The status will exit, and the value will be saved, when there is no key operation for 30 seconds.
If parameter U99 value is not “0000”, the password (the value of U99) is required to enter into parameter setting status:
AfterPdepressed for 3 seconds, display shows “---0”.
Pressto select the digit of password, pressto set the value of the digit.
After 4 digits are set, pressSto enter the password.
If the password is correct, enter into the parameter setting status. Else exit.
System parameter table:
Code
Function
Range
Factory
Setting
U10
Set-point (SP)’s low limit
-40.0 ~ 130.0
-40.0
U11
Set-point (SP)’s high limit
-40.0 ~ 130.0
130.0
U12
Low temperature warning point (relative)
0.0 ~ 130.0
35.0
U13
High temperature warning point (relative)
0.0 ~ 130.0
130.0
U14
Hysteresis
0.0 ~ 20.0
0.2
U30
Sensor calibration value
-20.0 ~ +20.0
0.0
U40
Output R2 timer on period’s time unit
0 ~ 2
1
U41
Output R2 timer on period’s time
1 ~ 9999
120
U42
Output R2 timer off period’s time unit
0 ~ 2
1
U43
Output R2 timer off period’s time
1 ~ 9999
120
U46
Output R2 working mode
0 ~ 2
0
U60
External input warning working mode
0 ~ 2
0
U70
PID proportional coefficient Kp
0.1 ~ 999.9
2.6
U71
PID integration coefficient Ti
0 ~ 999.9
500
U72
PID differential coefficient Td
0 ~ 999.9
50
U73
PID output amplitude
10 ~ 100%
50%
U74
Control method
0 ~ 1
0
U99
Password
0000 ~ 9999
0000
Control
Timer output R2
During timer on period (U41, U40), the R2 will be energized.
During timer off period (U43, U42), the R2 will be de-energized.
Temperature control
PID control (U74 = 0)
PID control. The output for heater is R1.
Hysteresis control (U74 = 1)
When measured ≥ Set-point (SP), R1 de-energized. When ≤ Set-point (SP) U14, R1 100% energized.