Suzhou Lily Tech. Co., Ltd.
Page 2, Total 4 Pages
Set system parameters
Keep〖P〗depressed for 3 seconds to enter into parameter setting status:
blinks, dispay shows “U10”, the 1
st
system parameter code.
Press〖▲〗or〖▼〗to select parameter code.
Press〖S〗to show the value of the parameter.
Press〖▲〗or〖▼〗to the value of the parameter.
Press〖S〗to return back to parameter code selection.
In this way, we can check and/or set all parameters.
Keep〖P〗depressed for 3 seconds to save and exit the status.
The status will exit, and the value will be saved, when there is no key operation for 30 seconds.
If parameter U99 value is not “0000”, the password (the value of U99) is required to enter into parameter setting status:
After〖P〗depressed for 3 seconds, display shows “---0”.
Press〖▼〗to select the digit of password, press〖▲〗to set the value of the digit.
After 4 digits are set, press〖S〗to enter the password.
If the password is correct, enter into the parameter setting status. Else exit.
System parameter table:
Set-point (SP)’s low limit
Set-point (SP)’s high limit
Low temperature warning point (relative)
Absolute low temperature warning point: SP - U12
High temperature warning point (relative)
Absolute high temperature warning point: SP + U13
Only effective when U74 = 1
Output R2 timer on period’s time unit
0: Second; 1: Minute; 2: Hour
Output R2 timer on period’s time
Output R2 timer off period’s time unit
0: Second; 1: Minute; 2: Hour
Output R2 timer off period’s time
0: Timer on/off;
1: Over temperature protection;
2: Timer on/off + Over temperature protection
External input warning working mode
0: Disable; 1: Normal open; 2: Normal close
PID proportional coefficient Kp
PID integration coefficient Ti
PID differential coefficient Td
Percent of full heater power rate.
0: PID control; 1: hysteresis control
If 0000, password disabled
Control
Timer output R2
During timer on period (U41, U40), the R2 will be energized.
During timer off period (U43, U42), the R2 will be de-energized.
Temperature control
PID control (U74 = 0)
PID control. The output for heater is R1.
Hysteresis control (U74 = 1)
When measured ≥ Set-point (SP), R1 de-energized. When ≤ Set-point (SP) – U14, R1 100% energized.