Suzhou Lily Tech. Co., Ltd.
www.suzhoulily.com.cn/en Page 1, Total 2 Pages
ZL-6200A Temperature Controller
Instruction Manual A1.0
Introduction
ZL-6200A is for cooling, heating or warning control. Front panel water proof level IP65, control resolution 0.1, keypad password
protection. It is suitable to control or audit cold storage, aquarium, water heater, and so on.
Main Function
Cooling, heating or auditing
Over temperature warning
Sensor failure warning
Temperature control
Temp. output energized/de-energized periodically when
sensor fails
Specification
Power supply: 185 ~ 245Vac, 50/60Hz
Sensor: NTC, 1.5 meters long
Display range: -50 ~ 120
Setting range: -50 ~ 120
Resolution: 0.1
Absolute accuracy: 1% at 25
Accuracy after calibration: 0.1
Temp. output, R1: 7A, 250Vac (pure resistance load)
Warning: Buzzing
(When in warning mode, temp. output as warning output)
Working: -10 ~ 45, 5 ~ 90%RH without dew
Dimension: W78 x H34.5 x D71 (mm)
Installation drilling: W71 x H29 (mm)
Case materials: PC + ABS fire proof
Protection level: IP65 (Front side only)
Keypad and Display
Display
Function On Blinking
Heating mode Heating mode Setting set-point
Cooling mode Cooling mode Setting set-point
AUX Warning mode Warning mode Setting set-point
Temp. output, R1 R1 energized Delay protecting
Warning ---- Warning
E1 Warning ---- Sensor open
E2 Warning ---- Sensor short
HH Warning ---- Over high temperature limit
LL Warning ---- Bellow low temperature limit
Operation
On/off: KeepSdepressed for 3 seconds to switch on/off.
Check settings: Press to check the set-point; Press to check the hysteresis.
Set Set-Point
KeepSdepressed for 3 seconds to enter into the set status. The current set-point value displays.
Pressor to set the value (keeping depressed can fast set).
KeepSdepressed for 3 seconds to exit, and save the settings.
The status will exit, and the setting will be saved, if no key operation within 30 seconds.
Set System Parameters
KeepPdepressed for 3 seconds: If the password is not “0000”, digits show “---0”, else enter into parameter setting status.
Pressto select the digit of the password, pressto set the value of the digit.
PressS to confirm:
If the password is correct, enter into the parameter setting status, else exit.
Set in parameter setting status:
Pressorto select the parameter code (see parameter code table below).
PressS to display the value of the code.
Question and Answer IconNeed help?

Do you have a question about the Lilytech ZL-6200A and is the answer not in the manual?

Lilytech ZL-6200A Specifications

General IconGeneral
BrandLilytech
ModelZL-6200A
CategoryTemperature Controller
LanguageEnglish

Summary

Introduction to ZL-6200A Controller

Main Controller Functions

Highlights core capabilities like cooling, heating, auditing, and warnings.

Controller Specifications

Details power, sensor, temperature ranges, and physical attributes.

Keypad and Display Elements

Explains the function of display indicators and warning codes.

Operating Procedures

Guides on turning on/off, setting temperature, and system parameters.

Controller Configuration and Control

Parameter Code Table

Lists and defines configurable parameters F0 through F6.

Control Logic Explained

Details how cooling, heating, and warning modes operate.

Output Load Delay Protection

Ensures timing delays for R1 output activation.

Installation and Safety Precautions

Physical Installation Steps

Guidance on mounting the controller into its housing.

Critical Safety Warnings

Important notes on wiring, connections, and environmental factors.

Electrical Wiring Diagram

Schematic showing terminal connections for R1 and power.