Technical data for the motors
LM 24 A LM 230 A
Power supply ............................. AC 19,2–28,8 V, 50/60 Hz AC 85–265 V, 50/60 Hz
DC 19,2–28,8 V
Power consumption .................. 1 W 1,5 W
For wire sizing ........................... 2 VA 4 VA
Connection ................................ Cable 1 m, 3×0,75 mm2 Cable 1 m, 3×0,75 mm2
Operating angle ......................... Max. 95°, adjustable 0–100% Max. 95°, adjustable 0–100%
Torque at rated voltage.............. Min. 5 Nm Min. 5 Nm
Direction of rotation ................... Switch selectable Switch selectable
0 or 1 0 or 1
Position indication ..................... Mechanical Mechanical
Running time for 95° ................. 150 s 150 s
Sound power level ..................... Max. 35 dB (A) Max. 35 dB (A)
Protection class ......................... III Safety extra-low voltage II Safety insulated
Protection type .......................... IP 54 IP 54
Ambient temperature range ...... -30 to +50°C -30 to +50°C
Ambient moisture ...................... 95 % RH 95 % RH
+
1
23
0
1
+
1
2
0
3
0
1
Technical data for the motor
LM 24 A-SR
Power supply ............................. AC 24 V, 50/60 Hz
DC 24 V
Power consumption .................. 1 W vid nominellt vridmoment
For wire sizing ........................... 2 VA
Connection ................................ Cable 1 m, 4×0,75 mm
2
Operating angle ......................... Max. 95°, adjustable 0–100%
Torque at rated voltage.............. Min. 5 Nm
Direction of rotation ................... Switch selectable
0 eller 1
Position indication ..................... Mechanical
Running time for 95° ................. 150 s
Sound power level ..................... Max. 35 dB (A)
Protection class ......................... III Safety extra-low voltage
Protection type .......................... IP 54
Ambient temperature range ...... -30 till +50°C
Ambient moisture ...................... 95 % RF