FAQ
Does the EVO have Closed Loop Torque Control capability?
ONLY EVO 8000 series can do Closed Loop Control, EVO 6000 and 6800 only supports SVVC and V/F
Does the EVO have PM Motor Control capability?
PM motors require very precise timing and filters to operate without damaging motor. Only 8000 series
have PM mode
What is the recommended Fuse or Breaker size?
It is recommended that a fast-acting current limiting Fuse is used because breakers may react too slow
and damage the drive. Rules in the NEC specific to VFDs call for the breaker to be 125% of the INPUT
current of the VFD (use rated current on the nameplate depending on the Duty Cycle) (for single phase
input current, * 1.5 is the fuse size).
What is the EVO’s voltage tolerance?
EVO Voltage tolerances are +/- 15%
Do we need Brake Kits AND a Braking Resistor?
6000 needs kit and brake resistor to dissipate heat
6800 just needs resistors, we have size recommendation if customer needs them
What is the Maximum Overload Capacity (for dynamic Braking)?
150% for 1 minute every 10 minutes.
Can we disable Input Phase Loss Protection?
Yes, set P7-00 to 0 (default is 1)