152
Parameter
Name
Description
Unit
end
05: Fast Stop (multi-function terminal input or keypad)
06: b1-10 (Run command at power up)
07: During baseblock when coast to stop with timer
08: Frequency command is less than d1-08 (Minimum
Output Frequency) during baseblock.
09: Waiting for ENTER command.
U3-17
Drive Overload
Estimate (oL2)
Displays the value of the drive overload detection
accumulator. An oL2 will be triggered when reaching 100%.
1%
U4: PID Monitors
U4-00
PID Feedback
Displays the PID feedback value as a percentage of the
maximum output frequency.
0.01%
U4-01
PID Input
Displays the PID input value as a percentage of the maximum
output frequency.
0.01%
U4-02
PID Output
Displays the PID output value as a percentage of the
maximum output frequency.
0.01%
U4-03
PID Target
Displays the PID target value as a percentage of the maximum
output frequency.
0.01%
U4-04
PID Differential
Feedback
Displays the difference of both feedback values when 10 is set
to both E3-01 and E3-07.
0.01%
U4-05
PID Feedback 2
Displays the adjusted feedback value if differential feedback is
used (U4-00 to U4-04)
The value in U4-00 and U4-05 will be the same if differential
feedback is not used.
0.01%
U4-08
PID Output 2
Displays PID control output(100% is the max. frequency)
0.01%