D0920 Arc-Detection Unit Rev. 0-D-070616
www.littelfuse.com • © 2016 Littelfuse •
• 13/18
Environment:
Operating Temperature: -25 to 70°C (-13°F to 158°F)
Storage Temperature: -25 to 70°C (-13°F to 158°F)
Humidity: 93% Non-Condensing
EMC Tests:
Verification tested in accordance with EN60255-26:2009.
1 MHz Burst: IEC 60255-22-1
± 1 kV differential mode
(line-to-line)
± 2.5 kV common mode
Electrostatic Discharge: IEC 60255-22-2
± 6 kV Contact Discharge
(direct and indirect)
± 8 kV Air Discharge
Radiated RF Immunity: IEC 60255-22-3
10 V/m, 80-1,000 MHz,
80% AM (1 kHz)
10 V/m, 1.4 to 2.7 GHz,
80% AM (1 kHz)
Fast Transient: IEC 60255-22-4
Class A: ± 4 kV
(on AC mains and I/O lines)
Surge Immunity: IEC 60255-22-5
± 1 kV differential mode
(on AC lines)
± 2 kV common mode
(on AC lines)
± 1 kV differential mode
(on I/O ports)
Conducted RF Immunity: IEC 60255-22-6
10 Vrms, 0.15-80 MHz,
80% AM (1 kHz)
Power Frequency: IEC 60255-22-7
Class A – 150 V Differential
Class A – 300 V Common Mode