D0920 Arc-Detection Unit Rev. 0-D-070616
www.littelfuse.com • © 2016 Littelfuse •
• 14/18
Magnetic Field Immunity: IEC 61000-4-8
50 Hz and 60 Hz
30 A/m and 300 A/m
Current Harmonics and Voltage
Fluctuations: IEC 61000-3-2
and IEC 61000-3-3
Class A
Radiated and Conducted
Emissions: CISPR 22:2008-09 / EN 55022:2010
Class B
Voltage Interruptions: IEC 60255-11 and IEC 60255-29
Interrupts 30%, 25 Cycles x 3
Interrupts 60%, 10 Cycles x 3
Interrupts 100%, 250 Cycles x 3
Certification: CE, European Union
EMC standards: EN60255-26
IEC 61010-1:2010 (3
rd
Edition)
Safety Requirements for Electrical Equipment
for Measurement, Control, and Laboratory
Use – Part I
4.2 A0220 Point Sensor
Sensor Type: Photo electric
Sensitivity: 0.5 mA / klux
Sensitivity Range: 2 to 30 klux
Sensitivity Area: 180 degrees, see Fig. 7
Cable Type: Shielded 2-wire, 24 AWG (0.2 mm
2
)
Cable Length: 10 m (33 ft) included, 50 m (164 ft) maximum, use
shielded 2-wire 20 AWG (0.5 mm
2
) when extending
length
IP Rating: IP65
Operating Temperature: -25 to 70°C (-13°F to 158°F)
Storage Temperature: -25 to 70°C (-13°F to 158°F)