EasyManua.ls Logo

LMF Clima LCE - Menu Set List; Alarm Folder and Error Handling; Modbus Communication Protocol

LMF Clima LCE
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Light Electronic Control DzLCEdz User Manual
Light control manual-ENG-neutro_03.docx Rev. 04 EN 4 / 6
firmware 2.4
EN
Serv: in this section there is the controller configuration
o PWD: insert service password (1)
o Pcfg: plant configuration
0= 2 pipes system, unique changeover coil
1= 2 pipes system, cooling coil + electric heater
2= 4 pipes system, cooling coil + heating coil
o Rprop: regulation probe
0= supply air sensor
1= display sensor
Menu Set List
Press button Set
Manual summer set-point
Manual winter set-point
Alarm folder:
o Er01: Regulation sensor failure; effects:
The unit is turned off
Automatic reset alarm
o Er02: External air sensor failure; effects:
Free-cooling mode disabled
Automatic reset alarm
o Er03: Display sensor failure; effects:
If Rprop=1 the unit is turned off
If Rprop=0 alarm not shown
o Er04: Dirty filter alarm; effect
None
o Er05: Electric heater over-temperature; effects:
Electric heater disabled
Fan activated
Modbus
Modbus type Holding Register
Read command: 03 (03Hex)
Write command: 16 (10Hex)
To modify the modbus communication protocols do as follows:
connect via Modbus through the RS-485 port with default protocols:
address= 1
baud rate= 9600
parity= EVEN
Word length= 8 (not editable)
Stop bits= 1 (not editable)
modify as you need the protocols writing the following address:
53274= address (1-255)
53275= baud rate
3= 9600 baud (default)
4= 19200 baud
5= 38400 baud
6= 58600 baud
7= 115200 baud
53276= parity
1= EVEN (default)
2= NONE
3= ODD
To activate the changes reboot the controller.
Net wiring example
Cable
Gray: GND
White: +
Black: -

Related product manuals