May, 2013 Page 29 of 52 949-1194 Rev. 7
P r o 9 Ramp/Soak: Select O n or O F F
O n Allows Programmed Ramp/Soak function to be started by the Run/Hold
key on the control front panel.
O F F Turns Ramp/Soak function O F F and resets program to beginning.
P S E t Programmer function set: Select O n or O F F .
O F F Skip Ramp/Soak Programming. Go to next Secondary Menu Item, InPC
(next page).
O n Enable Ramp/Soak Programming.
S t A t Programmer Status Display in the Primary Menu when Prog (above) is On:
Select O n or O F F .
O F F The Primary Menu operates as normal.
O n The Primary Menu is altered to have the following items inserted before
the SP1 menu item:
#### t i time remaining in active segment
#### ##t i total time in active segment
#### ##S P segment target set point
t b A S Ramp/Soak Time Base: Select 1 _ S or 6 0 _ S .
1 _ S Ramp/Soak time base is in 1 second increments. Program time 1 t i ...1 6 t i
is measured in seconds.
6 0 _ S Ramp/Soak time base is in 60 second increments (minutes). Program
time 1 t i . . . 1 6 t i is measured in minutes.
The following items repeat in the following order: 1 t i , 1 S P , 1 A 1 and 1 A 2 (if A L 1 is
programmed as E U n t ), 2 t i , 2 S P , 2 A 1 , 2 A 2,..., 1 6 t i , 1 6 S P , 1 6 A 1 1 6 A 2 ,. To avoid repetition
each item will only be described once.
1 t i Segment Time: Select 0 to 9 9 9 9 units (minutes if t b A S is set to 6 0 _ S , seconds if
t b A S is set to 1 _ S ).
1 S P Segment Set Point: Set to target value desired.
1 A 1 Segment Alarm 1 Event: Select O n or O FF .
O n Alarm 1 is active during segment 1 time (1 t i ).
O F F Alarm 1 is inactive during segment 1 time (1 t i ).
1 A 2 Segment Alarm 2 Event: Select O n or O FF .
O n Alarm 2 is active during segment 1 time (1 t i ).
O F F Alarm 2 is inactive during segment 1 time (1 t i ).
P E n d Program End action: Select H o l d or O o F F .
H o l d Stay at the Present Set Point (1 6 S P ).
O o F F Turn Off SP1 and SP2 Outputs at the end of the program.
L o o P Repeat program starting at 1 t i .
S P 1 Revert to S P 1 value.
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Love Controls 2600 SERIES and is the answer not in the manual?

Love Controls 2600 SERIES Specifications

General IconGeneral
BrandLove Controls
Model2600 SERIES
CategoryController
LanguageEnglish