Trouble information
Installation Dimension
3
Protection show Description
Overcurrent O-L
Undercurrent Und
Reverse phase r-P
Phase Loss P-F
Phase
unbalance
P-F
STALL StL
LOCK Loc
Instantaneous
Current
Sho
Ground fault g-F
Alert Bar-Leds
More than set current
Within the set time
Lower than the undercurrent set ratio
Within 3S
Within 0.1S
Over 70% of the rate of
unbalance : Within 3S
Over 50% of the rate of
unbalance : Within 5S
180% than seting current within 5S
More than the lock set current
ratio : Within 0.5S
More than the instantaneous set
current ratio : Within 0.1S
More than the set ground current
within the set time
Load Ratio(60~110%)
DMP 06 S E Z 220
Current
06
60
0.5~6.0A
5.0~60A
Wiring
S Screw
T Tunnel
TYPE
E Separate
- Unify
control Volt.
220 AC220V
110 AC110V
OPTION
Z Ground
I Instant.
Ordering Method