Offending against the message will result in death or serious injury.
Incorrect handling of the device may result in minor injury or physical damage.
Compare product with order, check for missing or cracked parts due to transportation.
Installation, maintenance, and inspection should be performed by qualified engineers.
Be careful not to exchange main and display units in combining.
Indicates more than set current within the set time.
Indicates lower than the undercurrent set ratio within 3 seconds.
Detects reverse phase within 0.1 seconds.
Detects phase loss over 70% of unbalance within 3 seconds.
Detects phase unbalance over 50% within 5 seconds.
Indicates 180% than setting current within 5 seconds.
Detects more than lock set current ratio within 0.5 seconds.
Indicates more than instantaneous set current ratio within 0.1 seconds.
Detects more than set ground current within the set time.
Alerts via Bar-LEDs indicating Load Ratio (60~110%).