Power Up: DLP-507 363-205-401
Page 8 of 10 Issue 7, March 1997
47. Does
BAT DISCHG
indicator go off and
HIGH RATE CHG/ON
indicator light
on
BATTERY CHARGER
?
If
YES,
then proceed to Step
53.
If
NO,
then continue with Step
48.
48. Replace
BATTERY CHARGER
.
Response:
BAT DISCHG
indicator will light and remain lighted for a
period of time determined by charge state of batteries.
If
BAT DISCHG
indicator remains lighted for more than 4
minutes,
BCU PMN
(or
P/M
) and
ADU NE
indicators will also
light.
When
BAT DISCHG
indicator goes off, the
HIGH RATE
CHG/ON
indicator will light and, if
BCU PMN
(or
P/M
) and
ADU NE
indicators are lighted, they will go off after 4 min-
utes.
The
HIGH RATE CHG/ON
indicator will go off after a period
of time determined by charge state of batteries.
49. Press
HIGH RATE CHG
/
ACTIVATE
pushbutton on
BATTERY CHARGER
after
BAT DISCHG
indicator goes off.
Response:
BAT DISCHG
indicator will light and remain lighted for a
period of time determined by charge state of batteries.
If
BAT DISCHG
indicator remains lighted for more than 4
minutes,
BCU PMN
(or
P/M
) and
ADU NE
indicators will also
light.
When
BAT DISCHG
indicator goes off, the
HIGH RATE
CHG/ON
indicator will light and, if
BCU PMN
(or
P/M
) and
ADU NE
indicators are lighted, they will go off after 4 min-
utes.
The
HIGH RATE CHG/ON
indicator will go off after a period
of time determined by charge state of batteries.
50. Does
BAT DISCHG
indicator go off and
HIGH RATE CHG/ON
indicator light
on
BATTERY CHARGER
?
If
YES,
then proceed to Step
53.
If
NO,
then continue with Step
51.

Related product manuals