363-205-401 Power Up: DLP-507
Issue 7, March 1997 Page 9 of 10
51. Replace
BATTERY CHARGER
with
BATTERY CHARGER
removed previ-
ously.
Response:
BAT DISCHG
indicator will light and remain lighted for a
period of time determined by charge state of batteries.
If
BAT DISCHG
indicator remains lighted for more than 4
minutes,
BCU PMN
(or
P/M
) and
ADU NE
indicators will also
light.
When
BAT DISCHG
indicator goes off, the
HIGH RATE
CHG/ON
indicator will light and, if
BCU PMN
(or
P/M
) and
ADU NE
indicators are lighted, they will go off after 4 min-
utes.
The
HIGH RATE CHG/ON
indicator will go off after a period
of time determined by charge state of batteries.
52. Check wiring on power shelf using SD-7C119-01. Repeat procedure from Step
46
after locating and correcting trouble.
53. Has
HIGH RATE CHG
/
ACTIVATE
pushbutton been pressed on all
BATTERY
CHARGER
s?
If
YES,
then proceed to Step
55.
If
NO,
then continue with Step
54.
54. Go to next
BATTERY CHARGER
and repeat from Step
46.
55.
NOTE:
Performance of this step is optional because of the possibility of having to
return to remote terminal site the following day to complete test. The
HIGH RATE CHG/ON
indicator on
BATTERY CHARGER
may only be
lighted momentarily.
Does
HIGH RATE CHG/ON
indicator on
BATTERY CHARGER
go off within
24 hours?
If
YES,
then proceed to Step
57.
If
NO,
then continue with Step
56.
56. Replace
BATTERY CHARGER
and repeat from Step
1.