Conversions: DLP-506 363-205-401
Page 2 of 6 Issue 7, March 1997
Table A
AUB27 Switch Setting
Function S1 Switch Position Function
No Protection Line (
NPL
) 1 Protection Line (
PL
)
Mode 2 Operation (
2
) 2 Mode 1 or FPC Operation (
4
)
(Always Use
4
Unless Equip-
ping FPB Mode 2)
AB In-Service (
ABI
) 3 AB Pre-Service (
ABP
)
CD In-Service (
CDI
) 4 CD Pre-Service (
CDP
)
AB Equipped (
ABE
) 5 AB Unequipped (
ABU
)
CD Equipped (
CDE
) 6 CD Unequipped (
CDU
)
Major Alarm for MISC1 (
1MJ
) 7 Minor Alarm for MISC1 (
1MN
)
Major Alarm for MISC2 (
2MJ
) 8 Minor Alarm for MISC1 (
2MN
)
Function S2 Switch Position Function
16 Bit Alarm Field (
16
) 1 13 Bit Alarm Field (
13
) (Al-
ways Use
13
)
FS Framing (
FS
) * (Use
FS
for FPB Mode 1 or 2)
2 ESF Framing (
FE
) † (Use
FE
for FPC-AutoCut)
No Cutover Hunting (
NC
)
(Use
NC
for Mode 1 and 2 or
When FPC-AutoCut is in
Pre-Service)
3 Cutover Enabled (
CUT
) (Only
Use
CUT
When Establishing
End-to-End FPC-AutoCut
System)
(
SGL
) 4 (Always Use
DBL
)
(
PA
) 5 (Always Use
NPA
)
(
MJP
) 6 (Always Use
MNP
)
Function S3 Switch Position Function
Data Link (
DL
) (Always Use
DL
)
No Data Link (
NDL
)
Function Clear Norm Position Function
Clear Provisioning (Use
CLEAR
When ADU is First
Installed in New System)
Do Not Clear Provisioning
(Use
NORM
for In-Service
System)
S4, S5, S6, S7 Rotary Switches S8, S9, S10, S11
System ID Number (Always Set to 0)
* Use FS option for FPB Mode 1, Mode 2, and for integrated applications.
† Use FE option for FPC-AutoCut and FPC applications.