Conversions: DLP-509 363-205-401
Page 2 of 4 Issue 7, March 1997
5. Perform the following items to clear trouble:
At COT, check
LIU
options and replace
LIU
if options are correct.
At RT, check
ADU
options and replace
ADU
if options are correct.
At RT, check
LIU
options and replace
LIU
if options are correct.
6. After performing the above Step, did
LIU B
CLF
and
BCU B
indicators go off?
If
NO
, then continue with Step
7
.
If
YES
, then proceed to Step
8
.
7. Trouble on digital line associated with digroup B. Verify that digital pairs have
been connected to the proper outside plant cable pairs. Use 363-205-500 or
363-202-500 TOP fault-locating procedures to locate trouble.
8. Request COT personnel to install
LIU
circuit packs in
LIU D
slot.
Response: All alarms clear.
9. After COT installs
LIU D
, did all alarms clear?
If
NO
, then continue with Step
10
.
If
YES
, then
STOP. YOU HAVE COMPLETED THIS PROCEDURE.
10. Perform the following items to clear trouble:
At COT, check
LIU
options and replace
LIU
if options are correct.
At RT, check
ADU
options and replace
ADU
if options are correct.
At RT, check
LIU
options and replace
LIU
if options are correct.
11. After performing the above Step, did all alarm indicators go off?
If
NO
, then continue with Step
12
.
If
YES
, then
STOP. YOU HAVE COMPLETED THIS PROCEDURE.
12. Trouble on digital line associated with digroup D. Verify that digital pairs have
been connected to the proper outside plant cable pairs. Use 363-205-500 or
363-202-500 TOP fault-locating procedures to locate trouble.
13. Request COT personnel to install
TRU
for shelf group AB
Response:
LIU-A
,
LIU-B, and LIU-P
(if equipped)
CLF
LEDs go off.
Digroups
A
and
B
alarms clear on
BCU
with in 4 minutes.