EasyManua.ls Logo

Lutron Electronics Maestro MS-OPS2 1 Series - Wiring Diagram 1: Single Location Installation; Wiring Diagram 1: Single Location with Neutral; Wiring Diagram 1: Single Location without Neutral; Wiring Diagram 2: Single Location Installation

Lutron Electronics Maestro MS-OPS2 1 Series
23 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Maestro Sensor
369666f 9 09.05.19
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Switch with Occupancy / Vacancy Sensor
Continued on next page...
Wiring Diagrams
Single Location Installation (120 V~)
-OPS2 and -VPS2
Wiring Diagram 1- with Neutral
Occupancy
sensor switch
120 V~
50 / 60 Hz
White
Ground
Hot / Live
Neutral
Load
Bare
Black Black
Single Location Installation (120 V~)
1
-OPS5M, -OPS6M2-DV, -VPS5M, -VPS6M2-DV
Wiring Diagram 2 - with Neutral
120 V~
50 / 60 Hz
White
Ground
Hot / Live
Neutral
Load
Blue
1
Bare
Black Black
Occupancy
sensor switch
Single Location Installation (120 V~)
-OPS2 and -VPS2
Wiring Diagram 1- without Neutral
Occupancy
sensor switch
120 V~
50 / 60 Hz
Green-sleeved wire
Ground
Hot / Live
Neutral
Load
Bare
Black Black
1
When using controls in single location installations, tighten the blue terminal or cap blue wire. Do not connect the blue terminal / wire to any other
wire or to ground.
2
Only one occupancy sensor switch can be used per multi-location circuit.
3
A single standard mechanical 3-way switch or up to 9 companion switches may be connected to most occupancy sensor switches.
Standard mechanical 3-way switch cannot be combined with companion switch. Total blue terminal wire length may be up to 150ft (46m).
Single Location Installation (120 V~)
1
-OPS5M, -OPS6M2-DV, -VPS5M, -VPS6M2-DV
Wiring Diagram 2 - without Neutral
120 V~
50 / 60 Hz
Green-sleeved wire
Ground
Hot / Live
Neutral
Load
Blue
1
Bare
Black Black
Occupancy
sensor switch
Note: Connect green-sleeved wire to ground only in retrofit and
replacement applications.
Note: When a neutral connection is available, remove the green
sleeve and connect the white wire to neutral.
Note: Connect green-sleeved wire to ground only in retrofit and
replacement applications.
Note: When a neutral connection is available, remove the green
sleeve and connect the white wire to neutral.
9