Installation Instructions Occupant Copy14
Symptom Possible Causes
Troubleshooting
No communication with
GRAFIK Eye® control unit.
Wallstation buttons do not work;
LEDs do not track.
LEDs do not light.
Contact closure inputs or sensor
input do not produce the desired
result in the system.
Miswire or loose connection at the control link data lines 3 and 4.
Wallstation has not been programmed or has been programmed incorrectly.
Wallstation is miswired.
Wallstation is not powered.
Wallstation is not wired to the correct set of lights.
Wallstation is not programmed to the correct device.
Column is not programmed.
Miswire or loose connection at wallstation(s) or processor on the control link
common and power connections 1 and 2.
Wallstation has been programmed incorrectly.
Column is not programmed.
Miswire or loose connection at wallstation sensor/CCI connector.
Wallstation has not been programmed or has been programmed incorrectly.
Wallstation buttons do not function
as intended.
Wallstation has not been programmed or has been programmed incorrectly.