6/20
53799173-05
R407C HEAT PUMP SYSTEMS (DHPUE)
Single Phase Supply 230Volts - 50Hz Three Phase Supply 400Volts - 50Hz
INPUT FULL LOAD AMPS INPUT FULL LOAD AMPS
MODEL
COMBINATION
STD.
MODEL
+ ELECT
Heating
STD.
MODEL
+ ELECT
Heating
SYSTEM
MAX.
STARTING
CURRENT
STD.
MODEL
+ ELECT
Heating
STD.
MODEL
+ ELECT
Heating
SYSTEM
MAX.
STARTING
CURRENT
IMPACT + DHPUE kW kW AMPS AMPS AMPS kW kW A/PH A/PH* A/PH
20(E) + 15 1.3 2.2 4.6 8.1 23 -- -- -- -- --
40(E) + 30 1.8 3.5 9.1 16.1 46 1.7 3.5 3.9 10.9 28
60(E) + 50 2.5 5.0 11.7 22.1 65 2.5 5.0 5.3 15.7 38
* Max Phase
ELECTRICAL LOADS (230V 50Hz 1Ph, A or 400V 50Hz 3PhN, A/Ph)
IMPACT
20E 40E 60E
FAN MOTOR 0.2 0.3 0.4
ELECTRIC HEATER (AIR COND.) 3.5 7 10.4
ELECTRIC HEATER (HEAT PUMPS) 3.5 7 10.4
FUSES
The system and its supply/interconnecting wiring must be protected by fuses, preferably High Rupture
Current (HRC) motor rated types (EN60269) or miniature circuit breakers (EN60898) or local codes having
similar time lag characteristics, that allow starting of the compressor yet still afford close overcurrent
protection under running conditions. The ratings below are for HRC motor rated fuses.
FUSES FOR SYSTEMS WITH SINGLE PHASE (230V) OUTDOOR UNITS (A)
IMPACT (E)
20 40 60
MCU+ or
DCU+
S H S H S H
15
16 16
30
16 16
40
20 20 20 20
60
20 20
MHPUE or
DHPUE
S H S H S H
30
10 16
50
20 20
S = Standard H = Heaters
FUSES FOR SYSTEMS WITH THREE PHASE (400V) OUTDOOR UNITS (A/Ph)
IMPACT (E)
40 60
MCU+ or
DCU+
S H S H
30
10 10
40
10 10 16 16
60
10 16
MHPUE or
DHPUE
S H S H
30
10 16
50
10 16
S = Standard H = Heaters