22
31
Battery equalization voltage
Available options for 24V model:
29.2V (default)
Setting range is from 25.0V to
31.5V. Increment of each click
is 0.1V.
Available options for 48V model:
58.4V (default)
Setting range is from 48.0V to
61.0V. Increment of each click
is 0.1V.
33
Battery equalized time
60min (default)
Setting range is from 5min to
900min. Increment of each
click is 5min.
34
Battery equalized timeout
120min (default)
Setting range is from 5min to
900 min. Increment of each
click is 5 min.
35
Equalization interval
30days (default)
Setting range is from 0 to 90
days. Increment of each click
is 1 day
36
Equalization activated
immediately
Enable
Disable (default)