Backlight control
Backlight on (default)
Backlight off
22
Beeps while primary source
is interrupted
Alarm on (default)
Alarm off
23
Overload bypass:
When enabled, the unit will
transfer to line mode if
overload occurs in battery
mode.
Bypass disable (default)
Bypass enable
25
Record Fault code
Record enable (default)
Record disable
26
Bulk charging voltage
(C.V voltage)
Available options for 24V model:
28.2V (default)
If user-defined is selected in
program 5, this program can
be set up. Setting range is
from 25.0V to 31.5V.
Increment of each click is
0.1V.
Available options for 48V model:
56.4V (default)
If user-defined is selected in
program 5, this program can
be set up. Setting range is
from 48.0V to 61.0V.
Increment of each click is
0.1V.