AC input voltage range
Appliances (default)
If selected, acceptable AC input
voltage range will be within
90-280VAC for output voltage at
220/230/240Vac or 65-140VAC for
output voltage at 101/110/120Vac.
UPS
If selected, acceptable AC input
voltage range will be within
170-280VAC for output voltage at
220/230/240Vac or 85-140VAC for
output voltage at 101/110/120Vac.
03
Output voltage
101Vac
If selected, acceptable feed-in grid
voltage range will be 89~111VAC.
110Vac
If selected, acceptable feed-in grid
voltage range will be 97~121VAC.
120Vac(Default)
If selected, acceptable feed-in grid
voltage range will be 106~132VAC.
220Vac
If 220Vac, 230Vac or 240Vac is
selected for output voltage, please
also set up country customized
regulations in program 34 to
determine acceptable feed-in grid
voltage and frequency range.
230V (Default)
240Vac
04
Output frequency
50Hz (default)
If choosing 101, 110 or 120Vac in
program 03 and 50Hz is selected
here, output frequency is 50Hz and
acceptable feed-in grid frequency
range will be 47.5~51.5Hz.
If choosing 220, 230 or 240Vac in
program 03 and 50Hz is selected
here, the output frequency is 50Hz.
60Hz
If choosing 101, 110 or 120Vac in
program 03 and 60Hz is selected
here, output frequency is 60Hz and
acceptable feed-in grid frequency
range will be 57.5~61.5Hz.
If choosing 220, 230 or 240Vac in
program 03 and 60Hz is selected
here, the output frequency is 60Hz.
05
Solar supply priority
Solar energy provides power to
charge battery as first priority.