Day/Night Mode
The day/Night mode allows you to enable / disable the timing of the
pre-alarm in the Central Panel. By factory setting, the central act
in “Night Mode” (without timing of pre-alarm).
To enable the general delay (Day Mode) you should:
1. Activate the keyboard
2. Press the button to “Day / Night” to switch to the desired status
3. In the display shows the message “Day Mode Active” or “Day Mode Off”
4. If the Day Mode stays active the LED “Delay” should light up getting fixed.
ADVANCED PROGRAMMING - LEVEL 3
The Level 3 Advanced Programming allows parameterize detail the functioning of Crossfire LCD.
This level is locked by password, and should only be used by qualified professionals for this purpose.
To enter in programming mode should:
1. Activate the keyboard
2. Access Menu 5 “Programming Mode”.
3. Insert the password according to the scheme using the cursor keys. After introduction of 4 digits
you should hear a double BIP in case of entry the correct code. In this case the LED “Keyboard”
should start blinking. If the code is wrong, you should hear a long bip. After finishing this sound,
you can reintroducing the access code.
Note: The code of the factory setting is: 1,2,3,4.
The advanced setup menu is tree-structured, and is composed by 7 top menus:
1 - Zones
2 - Times
3 - Test Mode
4 - Programming Code
5 - Language
6 - Installer Mode
7 - Factory Values
The features associated with each of the menus are described below. The navigation between menus
is processed according to the detailed description on page 9.
ZONES
MENU 1-1 Zone Types
The Menu “Zone Tipes” allows you to set each zone as “Automatic”
or “Intelligent”.
Automatic Zones always always respect the timing of pre-alarm, when the Control Panel is in “Day Mode”
ie with delays assets.
Intelligent Zones ignore the timing of pre-alarm regardless of this being active or not.