Installation into the water heating system
For intake and and drainage of water into the system of floor (central) heating, 1"
boiler connector are provided.
Stove may be mounted on closed or open central heating system.
Mounting on closed central heating system
One of the installations is depicted on the fig. 5.
- Safety valve must be installed in the vicinity of boiler and must be set to the
pressure of max. 3 bar (boiler is tested for 4 bars). Connection guide of safe valve
must be as shorter as possible and may not have capability of closing. In this guide,
also, may not be any valve beither any other armature.
- closed expansion vessel is to be installed close to the boiler and his safety valve is
short. Capacity of this vessel is determined based on the capacity of the boiler with
the proportion 1kW:1l.
- Installation of safety thermal valve of the boiler is mandatory on prescribed
position. We recommend safety thermal valve Caleffi 544.