EasyManuals Logo
Home>McQuay>Air Compressor>AGS 225D

McQuay AGS 225D User Manual

McQuay AGS 225D
82 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #7 background imageLoading...
Page #7 background image
OM AGSD-1 7
High Saturated Condenser – Hold Value
High Cond Hold Value = Max Saturated Condenser Value – 5 degrees F
This function prevents the compressor from loading whenever the pressure approaches
within 5 degrees of the maximum discharge pressure. The purpose is to keep the
compressor online during periods of possibly temporary elevated pressures.
High Saturated Condenser – Unload Value
High Cond Unload Value = Max Saturated Condenser Value – 3 degrees F
This function unloads the compressor whenever the pressure approaches within 3 degrees of
the maximum discharge pressure. The purpose is to keep the compressor online during
periods of possibly temporary elevated pressures.
Light Load Stg Dn Point
The percent load point at which one of two operating compressors will shut off, transferring
the unit load to the remaining compressor.
Load Limit
An external signal from the keypad, the BAS or a 4-20 ma signal that limits the compressor
loading to a designated percent of full load. Frequently used to limit unit power input.
Load Balance
Load balance is a technique that equally distributes the total unit load among the running
compressors on a unit or group of units.
Low Ambient Lockout
Prevents the unit from operating (or starting) at ambient temperatures below the setpoint.
Low Pressure Unload Setpoint
The psi evaporator pressure setting at which the controller will unload the compressor until
a preset pressure is reached.
Low Pressure Hold Setpoint
The psi evaporator pressure setting at which the controller will not allow further compressor
loading.
Low/High Superheat Error
The difference between actual evaporator superheat and the superheat target.
LWT
Leaving water temperature. The “water” is any fluid used in the chiller circuit.
LWT Error
Error in the controller context is the difference between the value of a variable and the
setpoint. For example, if the LWT setpoint is 44F and the actual temperature of the water
at a given moment is 46F, the LWT error is +2 degrees.
LWT Slope
The LWT slope is an indication of the trend of the water temperature. It is calculated by
taking readings of the temperature every few seconds and subtracting them from the
previous value, over a rolling one minute interval.
ms
Milli-second
Maximum Saturated Condenser Temperature
The maximum saturated condenser temperature allowed is calculated based on the
compressor operational envelope.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the McQuay AGS 225D and is the answer not in the manual?

McQuay AGS 225D Specifications

General IconGeneral
BrandMcQuay
ModelAGS 225D
CategoryAir Compressor
LanguageEnglish

Related product manuals