OM AGSD-1 77
Operating Limits:
Maximum standby ambient temperature, 130F (55C)
Maximum operating ambient temperature is 115F (46C), or 125F (52C) with the addition of
the optional high ambient package
Minimum operating ambient temperature (standard), 35F (2C)
Minimum operating ambient temperature (with optional low-ambient control), 0F (-18C)
Leaving chilled water temperature, 40F to 60F (4.4C to 15.6C)
Leaving chilled fluid temperatures (with anti-freeze), 30F to 60F (-2C to 16C). Unloading is
not permitted with fluid leaving temperatures below 30F (-1C).
Operating Delta-T range, 6 degrees F to 16 degrees F (3.3 degrees C to 8.9 degrees C)
Maximum operating inlet fluid temperature, 76F (24C)
Maximum non-operating inlet fluid temperature, 100F (38C)