48 AGZ 026B through 130B IOMM AGZ-5
Table 34, AGZ 075BB/BH – 130BB/BH, Electrical Data, Multi-Point (106°F)
Electrical Circuit #1 Electrical Circuit #2
Power
Supply
Power
Supply
Field Wire Field Wire
AGZ
Unit
Size
olts
Minimum
Circuit
Ampacity
(MCA)
Qty
Wire
Gauge
75C
Recomm’d
Fuse
or HACR
Breaker
Size
Max. Fuse
or HACR
Breaker
Size
Minimum
Circuit
Ampacity
(MCA)
Qty
Wire
Gauge
75C
Recomm’d
Fuse
or HACR
Breaker
Size
Max.
Fuse
or HACR
Breaker
Size
230 190 3 3/0 225 250 190 3 3/0 225 250
380 102 3 #2 125 125 102 3 #2 125 125
460 99 3 #3 110 125 99 3 #3 110 125
075B
575 76 3 #4 90 100 76 3 #4 90 100
230 190 3 3/0 225 250 211 3 4/0 250 250
380 102 3 #2 125 125 142 3 1/0 175 175
460 99 3 #3 110 125 111 3 #2 125 150
085B
575 76 3 #4 90 100 83 3 #3 100 110
230 211 3 4/0 250 250 211 3 4/0 250 250
380 142 3 1/0 175 175 142 3 1/0 175 175
460 111 3 #2 125 150 111 3 #2 125 150
090B
575 83 3 #3 100 110 83 3 #3 100 110
230 203 3 4/0 225 250 272 3 300 300 300
380 123 3 #1 150 150 159 3 2/0 175 200
460 101 3 #2 110 125 136 3 1/0 150 175
100B
575 83 3 #4 100 100 109 3 #2 125 125
230 272 3 300 300 300 272 3 300 300 300
380 159 3 2/0 175 200 159 3 2/0 175 200
460 136 3 1/0 150 175 136 3 1/0 150 175
110B
575 109 3 #2 125 125 109 3 #2 125 125
230 272 3 300 300 300 317 3 400 400 400
380 159 3 2/0 200 200 204 3 4/0 250 250
460 136 3 1/0 175 175 159 3 2/0 200 200
120B
575 109 3 #2 125 125 118 3 #1 150 150
230 317 3 400 400 400 317 3 400 400 400
380 204 3 4/0 250 250 204 3 4/0 250 250
460 159 3 2/0 200 200 159 3 2/0 200 200
130B
575 118 3 #1 150 150 118 3 #1 150 150
NOTES:
1. All Electrical Data notes are on page 49.
2. Conduit hubs are not supplied.