74 AGZ 026B through 130B IOMM AGZ-5
Important Messages
WARNING
WARNING HIGH VOLTAGE: Motor control equipment and electronic controllers are
connected to hazardous line voltages. When servicing drives and electronic controllers,
there may be exposed components with housings or protrusions at or above line
potential. Extreme care should be taken to protect against shock.
Stand on an insulating pad and make it a habit to use only one hand when checking
components. Always work with another person in case an emergency occurs.
Disconnect power before checking controllers or performing maintenance. Be sure
equipment is properly grounded. Wear safety glasses whenever working on electronic
controllers or rotating machinery.
WARNING
Wait at least five (5) minutes after turning OFF the input power supply before
performing maintenance or an inspection.
Otherwise, there is the danger of electric shock.
Introduction
This end of this section lists the parameters for the CR100 series inverters and the values as
programmed in the factory.
Unit identification
Parameter Settings for Keypad Entry
Main Profile Parameters
“F” Group Parameters
Function
Code
Name
McQuay
Setting
F_01 Output Frequency Setting
0.0
F_02 Acceleration (1)
10.0
F_03 Deceleration (1)
10.0
F_04 Keypad Run Key Routing
00