IOMM AGZ-5 AGZ 026B through 130B 85
If a word-type setpoint (for example, YES or NO) is to be selected, the choices are
loaded into the menu and selected by scrolling through the available setpoint
options using the UP ARROW key.
4. Enter the desired value or word into the controller by pressing the ENTER key.
Stated another way, once the desired set screen is reached, editing is accomplished by
pressing the ENTER key until the desired field is selected within the set screen. This
field is indicated by the cursor blinking on it. The arrow keys will then operate as
defined below.
CANCEL Reset the current field to the value it had when editing began.
DEFAULT Set value to original factory setting.
INCREMENT Increase the value or select the next item in a list.
DECREMENT Decrease the value or select the previous item in a list.
During edit mode, the display shows a two-character-wide menu pane on the right as
shown below. These characters relate to the functions shown above. After a field has
been set to the desired new values, press ENTER. This enters the value and scrolls to
the next field.
SET UNIT SPs (X) <D
(data) <C
(data) <+
(data) <-
Additional fields can be edited by pressing the ENTER key until the desired field is
selected.
Two four-digit passwords provide OPERATOR and MANAGER levels of access to
setpoints. The passwords are preprogrammed into the controller. The Operator
Password is 0100, the Manager Password is 2001. Either password must be entered
using the ENTER PASSWORD screen (15) before a protected setting can be changed.
This screen can be accessed either through the SET OTHER menu, or by simply
pressing the ENTER key while on one of the SET screens. The controller will
automatically go from the screen with the setting change to this screen. After the
correct password has been entered, the controller will automatically return to the
original set screen.
Once a password has been entered, it remains valid for 15 minutes after the last key-
press.
SET UNIT SPs (1)
Unit Enable=OFF
Mode=COOL
Source=KEYPAD
Unit Enable is an external signal, or a keypad setting, that keeps the unit off when the
setting is OFF, and allows it to run if there is a call for cooling when the setting is ON.
The source for the signal is selected in the 4
th
line and can be:
1. KEYPAD, in which case the selection is made in line 2 and would be normally
selected as ON. This is the normal setting when no external signals are controlling
the unit.
2. DIGITAL INPUT, in which an external switch is wired across terminals #52 and
#72. (See wiring diagram page 50).
3. BAS, used with BAS signal.