IOMM AGZ-5 AGZ 026B through 130B 87
SET UNIT SPs (8)
Units = °
°°
°F/psi
Lang = ENGLISH
Units settings are only °F/psi at the present time. °C/kPa will be available later.
Lang (Language) settings can be only ENGLISH at present.
SET UNIT SPs (9)
Protocol = MODBUS
Ident Number=001
Baud Rate=9600
SET UNIT SPs (10)
Evap Pressure Sensor
Cir1 Offset= XX.Xpsi
Cir2 Offset= XX.Xpsi
The pressure offsets on menus 10 and 11 and the temperature offsets on menus 12, 13
and 14 correct the controller's display of the parameters. The sensors used in these
units have a high degree of repeatability but may need initial correction (offset). An
accurate pressure gauge or thermometer is used to determine the correct temperature or
pressure. A positive or negative offset value is then entered to make the controller
reading agree with the measured value.
SET UNIT SPs (11)
Cond Pressure Sensor
Cir1 Offset= XX.Xpsi
Cir2 Offset= XX.Xpsi
SET UNIT SPs (12)
Suction Temp Sensor
Cir 1 Offset= XX.X
o
F
Cir 2 Offset= XX.X
o
F
SET UNIT SPs (13)
Leaving Evaporator
Water Temp Sensor
Offset= XX.X
o
F
SET UNIT SPs (14)
Outside Ambient
Temperature Sensor
Offset= XX.X
o
F