IOMM AGZ-5 AGZ 026B through 130B 43
Electrical Data - High Ambient
Table 29, AGZ 026BB/BH – 070BB/BH, Electrical Data, Single Point
Power Supply
Field Wire
AGZ Unit
Size
Volts
Minimum
Circuit
Ampacity
(MCA)
Quantity
Wire
Gauge
75C
Recomm’d.
Fuse
Or HACR
Breaker
Size
Max. Fuse
Or HACR
Breaker
Size
230 133 3 1/0 150 150
380 80 3 #4 90 90
460 68 3 #4 80 80
026B
575 53 3 #6 60 60
230 144 3 1/0 175 175
380 88 3 #3 100 100
460 74 3 #4 90 90
030B
575 59 3 #6 70 70
230 155 3 2/0 175 175
380 96 3 #3 110 110
460 80 3 #4 90 90
035B
575 64 3 #6 70 70
230 167 3 2/0 200 200
380 113 3 #2 125 125
460 84 3 #4 90 90
040B
575 70 3 #4 80 80
230 188 3 3/0 225 225
380 123 3 #1 125 125
460 94 3 #3 110 110
045B
575 78 3 #4 90 90
230 207 3 3/0 225 225
380 132 3 1/0 150 150
460 104 3 #2 125 125
050B
575 86 3 #3 100 100
230 229 3 4/0 250 250
380 147 3 1/0 175 175
460 115 3 #2 125 125
055B
575 96 3 #3 110 110
230 248 3 250 250 250
380 160 3 2/0 175 175
460 124 3 #1 150 150
060B
575 105 3 #2 125 125
230 282 3 300 350 350
380 164 3 2/0 200 200
460 138 3 1/0 175 175
065B
575 115 3 #2 125 125
230 304 3 350 350 350
380 172 3 2/0 200 200
460 150 3 1/0 175 175
070B
575 123 3 #1 150 150
NOTES:
1. Units operating in ambient temperatures above 95°F (35°C) must use the Maximum Fuse or
HACR Breaker size.
2. All Electrical Data notes are on page 49.
3. Conduit hubs are not provided.