Piping Works And Flaring Technique
Do not use contaminated or damaged copper tubing. If any pipings, evaporator or condenser had been exposed or had been
opened for 15 seconds or more, the system must be vacuumed. Generally, do not remove plastic, rubber plugs and brass
nuts from the valves, ttings, tubings and coils until it is ready to connect suction or liquid line into valves or ttings.
If any brazing work is required, ensure that the nitrogen gas is passed through coil and joints while the brazing work is
being done. This will eliminate soot formation on the inside walls of the copper tubings.
Cut the pipe stage by stage, advancing the blade of the pipe cutter slowly. Extra force and deep cut will cause more distortion
on the pipe and thus extra burr. See Figure A.
Cutting Copper Tube
Fig. B
Fig. A
Remove Burr
Fig. C
Copper Tube
Swaging Block
Remove burrs from cut edges of the pipes with remover
as shown in Figure B. This will avoid unevenness on the
are faces which will cause gas leak. Hold the pipe on
top position and burr remover at lower position to prevent
metal chips from entering the pipe.
• Insert the are nuts, mounted on the connection parts of
both the indoor unit and outdoor unit, into the copper
pipes.
The exact length of pipe protruding from the top surface of
the swaging block is determined by the aring tool. Refer
Figure C.
Fix the pipe rmly on the swaging block. Match the centers
of both the are die and the aring punch, and then tighten
the aring punch fully.
Piping Connection To The Units
Align the center of the piping and tighten the are nut
suf ciently with ngers. Refer Figure D.
Finally, tighten the are nut with the torque wrench until
the wrench clicks.
When tightening the are nut with the torque wrench,
ensure that the tightening direction follows the arrow
indicated on the wrench.
The refrigerant pipe connection are insulated by closed
cell polyurethane.
Spanar
Torque Wrench
Indoor Piping
Flare Nut
Flared Tube
Flare Joint
Fig. D
Ø Tube, D A (mm)
Inch mm Imperial
(Wing-nut Type)
Rigid
(Clutch Type)
1/4" 6.35 1.3 0.7
3/8" 9.52 1.6 1.0
1/2" 12.70 1.9 1.3
5/8" 15.88 2.2 1.7
3/4" 19.05 2.5 2.0
Pipe Size (mm/in) Torque (Nm/ft-lb)
6.35 (1/4) 18 (13.3)
9.52 (3/8) 42 (31.0)
12.70 (1/2) 55 (40.6)
15.88 (5/8) 65 (48.0)
19.05 (3/4) 78 (57.6)
1/4t
1 EN 5CKYER-1009(1).indd 131 EN 5CKYER-1009(1).indd 13 4/21/11 9:11:20 AM4/21/11 9:11:20 AM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the McQuay E Series and is the answer not in the manual?

McQuay E Series Specifications

General IconGeneral
BrandMcQuay
ModelE Series
CategoryInverter
LanguageEnglish

Related product manuals