• The outdoor unit must be installed in such a way, so as to prevent short circuit of the hot discharged air or obstruction to
the smooth air fl ow. Please follow the installation clearance shown in the fi gures below. Select the coolest possible place
where intake air temperature is not greater than the outside air temperature.
• Where a wall or other obstacles is in the path of outdoor unitʼs intake or exhaust airfl ow, follow the installation guidelines
below.
• For any of the below installation patterns, the wall height on the exhaust side should be 1200mm or less.
5SLY20/25C/CR
More than 50 More than 100
Side View
Top View
Top View
More than 50
More than 50
More than 50
More than 150
More than 100
More than 150
More than 300
Unit: mm
INSTALLATION OF THE OUTDOOR UNIT
Wall facing one side
More than 100 More than 350
More than 50
More than 50
Top View
Top View
Side View
More
than 100
More than 350
More than 100
More than 350
Unit: mm
5SLY28CR
1200
or less
More than 50
Wall facing two sides
Wall facing two sides
Wall facing one side Wall facing two sides
Wall facing three sides