EasyManua.ls Logo

McQuay FCVC

McQuay FCVC
82 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IM 1017/Page 61 © 2009 McQuay International 800-432-1342 www.mcquay.com
Table 3: Dip Switch Configuration
Note: * On is with the dip switch handle to the right. See diagram below.
Figure 3: Circuit Board
Service Menu:
Access: Press UP and DOWN arrows for 5 seconds.
Menu Selection: Select 1 to 5 by pressing the mode button or
by pressing the UP and DOWN arrows simultaneously.
Adjust Value: Use UP or DOWN arrow.
Table 4: Service Functions
Switch Closed On* Open Off
1 Not Used Not Used
2
Staged Heat
3°F Diff. (Term. 13)
Aux. Heat No Diff.
(Term. 13)
3 F Display C Display
4
Main & Sec. Outputs
0-10 VOC (Term. 10 & 11)
requires JP4 & JP5
Main & Sec. Outputs
4-20 mA (Term. 10 & 11)
Remove JP4 & JP5
5 Operating Position Not Used
6 Setback= 90°F & 50°F Setback = 85°F & 60°F
Item # Function Range Default
1 Zone Temp Offset -5.1 F to 5.1 F 0 F
2 Valve Stroke Time 30 sec. to 5 min. 120 sec.
3 Fan Delay to OFF 2 to 10 minutes 120 sec.
4
Compressor
Minimum Off Time
30 seconds to 10
minutes
120 sec.
5Purge Cycle
0 = time based
1 = temperature
based
1

Table of Contents

Related product manuals