EasyManuals Logo

McQuay MDS 150B User Manual

McQuay MDS 150B
166 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #80 background imageLoading...
Page #80 background image
74 Service Manual SM-MDS_(ii)
Outdoor pressure sensor error
Error Code: Decorative Error code #5, H5, L2, 35, 42 (For MC301), ER76 and ER77 (For MDS-M PCB)
Is the wire connection
to pressure sensor broken?
Replace the wire and restart the
system
NO
YES
Replace PCB
Turn off the unit
Is the resistance of the
pressure sensor normal?
Refer Appendix 7.3
NO
Replace the sensor and restart
the system
YES
NO
YES
Fix the port/replace PCB and
restart the system
Check the HS/LS port
on outdoor PCB. Normal?
6

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the McQuay MDS 150B and is the answer not in the manual?

McQuay MDS 150B Specifications

General IconGeneral
BrandMcQuay
ModelMDS 150B
CategoryCompressor
LanguageEnglish

Related product manuals