DC Inverter U-match Series Floor Ceiling Type Unit
20
Fig. 4.11
Fig. 4.12
Table 4.3 Flare nut tightening torque
Pipe Diameter
Tightening Torque
1/4 Inch
15-30 (m)
3/8 Inch
35-40 (m)
5/8 Inch
60-65 (m)
1/2 Inch
45-50 (m)
3/4 Inch
70-75 (m)
7/8 Inch
80-85 (m)
5.3.4 Connecting the Pipe at the Outdoor Side Unit
Tighten the flare nut of the connection pipe at
the outdoor unit valve connector. The tightening
method is the same as that as at the indoor side.
Fig. 4.13