ICLAMP SPECIFICATIONS
Measurement range: 1 mA to 1200 A
Transformation ratio: 1000 : 1
Output signal: 1 mA / A (1 A @ 1000 A)
Accuracy
1mA to 100 mA : 3% of reading
0.1 A to 1 A : 2% of reading
1 A to 10 A : 1% of reading
10 A to 100 A : 0.5% of reading
Operating temperature
-10°C to +50°C / 14°F to 122°F
0% to 85% RH at +35°C / 95°F
Storage temperature
-20°C to +70°C / -4°F to 158°F
Jaw opening: 57 mm maximum (2.3 in)
Maximum conductor size: 52 mm (2.1 in)
Insulation: Double insulation
Voltage rating: 600 V CAT III
Current rating: 1200 A for 20 minutes
Ingress protection: IP40
Safety
EN61010-2-032
EMC
EN 50081-1 Class B
EN 50082-2
Dimensions:
111 mm x 216 mm x 45 mm (4.4 in x 8.5
in x 1.8 in)
Weight: 0.5 kg approximately (1.2lb)
VCLAMP SPECIFICATIONS
Insulation: Double insulation
Voltage rating: 600V CAT III
Current rating: 1200A for 20 minutes
Ingress protection: IP40
Operating temperature
-10°C to +50°C / 14°F to 122°F
0% to 85% RH at +35°C / 95°F
Storage temperature
-20°C to +70°C / -4°F to 158°F
Jaw opening: 57mm maximum (2.3in)
Maximum conductor size: 52mm / 2.1in
Electrical safety
EN61010-2-032
EMC
EN 50081-1 Class B
EN 50082-2
Dimensions: 111mm x 216mm x 45mm
(4.4in x 8.5in x 1.8in)
Weight: 0.5 kg approximately (1.2 lb)

Other manuals for Megger DET4TR2